Defects in the Insulation
The measurement of insulation resistance is a common
routine test performed on all types of electrical wires and cables. As a
production test, this test is often used as a customer acceptance test, with
minimum insulation resistance per unit length often specified by the customer.
The results obtained from IR Test are not intended to be useful in finding localized defects in the insulation as in a true HIPOT test, but rather give information on the quality of the bulk material used as the insulation.
Even when not required by the end customer, many wire and
cable manufacturers use the insulation resistance test to track their
insulation manufacturing processes, and spot developing problems before process
variables drift outside of allowed limits.
Selection of IR Testers (Megger):
Insulation testers with test voltages of 500, 1000, 2500, and 5000 V are available. The recommended ratings of the insulation testers are
given below:
Voltage
Level |
IR
Tester |
650V |
500V
DC |
1.1KV |
1KV
DC |
3.3KV |
2.5KV
DC |
66Kv and above |
5KV
DC |
Test Voltage for Meggering:
When
AC Voltage is used, The Rule of Thumb is:
Test Voltage (A.C) = (2 X Name Plate Voltage) + 1000
When DC Voltage is used (Most used in all Megger)
Test Voltage (D.C) = (2 X Name Plate Voltage)
Equipment
/ Cable Rating |
DC
Test Voltage |
24V To 50V |
50V
To 100V |
50V To 100V |
100V
To 250V |
100V To 240V |
250V
To 500V |
440V To 550V |
500V
To 1000V |
2400V |
1000V
To 2500V |
4100V |
1000V
To 5000V |
Measurement Range of Megger:
Test
voltage |
Measurement
Range |
250V DC |
0MΩ
to 250GΩ |
500V DC |
0MΩ
to 500GΩ |
1KV DV |
0MΩ
to 1TΩ |
2.5KV DC |
0MΩ
to 2.5TΩ |
5KV DC |
0MΩ
to 5TΩ |
Precaution while Meggering:
Before Meggering:
Make
sure that all connections in the test circuit are tight. Test
the megger before use, whether it gives INFINITY value
when not connected, and ZERO when the two terminals are connected together and
the handle is rotated.
During Meggering:
Make
sure when testing for the earth, that the far end of the conductor is not touching,
otherwise, the test will show faulty insulation when such is not actually the
case.
Make
sure that the earth used when testing for earth and open circuits is a good one
otherwise the test will give wrong information. Spare conductors should not be
merged when other working conductors of the same cable are connected to the
respective circuits.
After completion of cable Meggering:
·
Ensure that all conductors have been
reconnected properly.
·
Test the functions of Points, Tracks and signals connected through the cable for their correct response.
·
In the case of signals, the aspect should be verified
personally.
·
In case of points, verify positions at the site.
Check whether any polarity of any feed taken through the cable has been earthed
inadvertently.
Safety Requirements for Meggering:
·
All equipment under test MUST be
disconnected and isolated.
·
Equipment should be discharged (shunted or
shorted out) for at least as long as the test voltage was applied in order to
be absolutely safe for the person conducting the test.
·
Never use Megger in an explosive atmosphere.
·
Make sure all switches are blocked out and
cable ends marked properly for safety.
·
Cable ends to be isolated shall be
disconnected from the supply and protected from contact to supply, or ground,
or accidental contact.
·
Erection of safety barriers with warning
signs, and an open communication channel between testing personnel.
·
Do not megger when humidity is more than 70
%.
·
Good Insulation: Megger reading increases
first then remains constant.
·
Bad Insulation: Megger reading increases
first and then decreases.
·
Expected IR value gets on Temp. 20 to 30
decree centigrade.
·
If the above temperature reduces by 10 degrees
centigrade, IR values will increase by two times.
·
If the above temperature increases by 70-degree
centigrade IR values decrease by 700 times.
How to use Megger
Meggers is equipped with three connections Line Terminal
(L), Earth Terminal (E), and Guard Terminal (G).
Megger Connections
Resistance is measured between the Line and Earth terminals, where current will travel through coil 1. The “Guard” terminal is provided for special testing situations where one resistance must be isolated from another. Let’s check one situation where the insulation resistance is to be tested in a two-wire cable.
To measure insulation resistance from a conductor to the
outside of the cable, we need to connect the “Line” lead of the megger to one
of the conductors and connect the “Earth” lead of the megger to a wire wrapped
around the sheath of the cable.
Megger configuration
In this configuration, the Megger should read the resistance between one
conductor and the outside sheath.
We want to measure Resistance between Conductor- 2 to
sheaths but actually megger measure resistance in parallel with the series
combination of conductor-to-conductor resistance (Rc1-c2) and the first
conductor to the sheath (Rc1-s).
If we don’t care about this fact, we can proceed with the
test as configured. If we desire to measure only the resistance between the second conductor and the
sheath (Rc2-s), then we need to use the megger’s “Guard”
terminal.
Megger - Connecting guard terminal
Connecting the “Guard” terminal to the first conductor
places the two conductors at almost equal potential.
With little or no voltage between them, the insulation
resistance is nearly infinite, and thus there will be no current between the two conductors.
Consequently, Megger’s resistance indication will be based exclusively on
the current through the second conductor’s insulation, through the cable
sheath, and to the wire wrapped around, not the current leaking through the first
conductor’s insulation.
The guard terminal (if fitted) acts as a shunt to remove
the connected element from the measurement. In other words, it allows you to be
selective in evaluating certain specific components in a large piece of
electrical equipment. For example, consider a two-core cable with a sheath.
As the diagram below shows there are three resistances to
be considered.
Meggerning wiring
If we measure between core B and the sheath without a
connection to the guard terminal some current will pass from B to A and from A
to the sheath. Our measurement would be low. By connecting the guard terminal
to A the two cable cores will be at very nearly the same potential and thus the
shunting effect is eliminated.
0 Comments