2.1 Summary

2.1.1 VOLTLOGIC-351 ARC controller is a new generation of digital relaying control terminal produced . It can protect, control, measure and monitor the grid with voltage below 35kV. It is suitable for a variety of system operating modes, including isolated neutral system, resistance-grounded system and arc suppression coils grounding system.


                                                    Figure1: VOLTLOGIC-351 Device Panel

VOLTLOGIC-351 series device collect full power value and isolate the measurement current circuit from the protection current circuit, which not only improve the reliability of protection but also ensures the measurement accuracy. High-precision measurement function ensures the factor of voltage, current and power to grade 0.2, as well as the factor of grade 0.5 to four- quadrant power measuring and metering.

VOLTLOGIC-351 series supports function of time setting. Two RS485 channels support for the double-net communication mode as well as the communication protocol of Modbus IEC60870-5-101 . DNP3.0 . It provides extremely reliable net communication for the users, for different protocols could be applied into different networks.

VOLTLOGIC-351 is able to restore four groups of setting value, which greatly facilitates different operating mode.

2.2 Main characteristics

Rich interface resources

The interface resources provided by VOLTLOGIC-351 are: the input passband of 7 channels AC current and 4 channel AC voltage. 10 channel switching value input passband (suitable for AC and DC), 7 channel switching value output; the communication interface has two RS485 and one RS232 maintenance ports.

Flexible and convenient connection method

The four AC voltage inputs of VOLTLOGIC-351 can connect with the phase voltage, Line voltage or zero-sequence voltage or unbalanced voltage, which adapt to a variety of PT Connection.

Highly reliable design

With the design principles of stable, reliable and durable, industrial components are adopted, all connections with the outside world are fully isolated as well as anti-lightning protection circuit and power filter are built in. Professional EMC design provides a fundamental guarantee for the reliability of operation through real-time monitoring towards the device input power, analog and digital power supply, as well as perfect self-check program. To monitor the input power helps VOLTLOGIC-351 to save the important data in good time before the power is removed.

event record in order

VOLTLOGIC-351 will provider users 200 pieces of SOE for fault analysis (100 is a circle, namely, the next first SOE will cover the 101 SOE), the resolution of SOE is 1ms. SOE can not only record various protection actions but also filtered switching value deformation, as well as other information for fault analysis, which includes power-on, power-down, reset, self-test error of device and signal reversion, remote operation, modification of protection valuation.

High-precision measurement

The measurement function of VOLTLOGIC-351 can measure IA, IB, IC, I0, Ua, Ub, Uc, Uab, Ubc, Uca, P , Q, F, fs, PF precisely and monitor the protection current Ia、Ib、Ic, as well as measurement towards forward kWh, reverse kWh, forward kVarh, forward kVarh. The measurement accuracy of voltage, current and power factor reaches to grade 0.2, the accuracy of power and electric degree reaches to grade 0.5. The maximum frequency measurement bias is ±0.01Hz calculation error caused by fundamental frequency fluctuation can be eliminated completely through adopting the frequency tracking technique, and real-time monitoring the changes of system frequency, as well as adjusting the time interval of data sampling.

Accurate time setting

VOLTLOGIC-351 has three types of time setting: time setting of artificial device panel, communication time setting. Among them, artificial instrument panel is rough time setting, generally for debugging; and the precision of communication time setting is less than± 100ms; Accurate time setting ensures the reliability of SOE information, and enhances their value in the fault analysis. Particularly, the clock accuracy will not be affected (the clock keeps on running) even when reset or short-term power-down occur.

 2.3 Performance index

 Rated data

  • Power: 110/220VDC or VAC , allowable deviation +15℅, -20℅; 
  • 24/48 VDC, allowable deviation +15℅, -20℅.
  • 220VDC or VAC gap break (IEC 60255-11) 100 ms device without losing power
  • AC voltage: 100V or 100/ 3 V, linear measurement range is 0.2V~150V.
  • AC current: 5A, 1A
  • Measuring linear range is 0.01A~6A(5A) or 0.002A~1.2A(1A);
  • Protecting linear range is 0.1A~120A(5A) or 0.02A~24A(1A);
  • I0 measuring linear range is0.02A~20A or 0.004A~4A is optional.
  • Frequency: 50Hz, the measurement range is 45.00 Hz~55.00 Hz.
  • OR 60Hz, the measurement range is 55.00 Hz~65.00 Hz
  • Phase sequence: ABC

 Power consumption
Power: normal<7W; exit actuation <10W
AC voltage: <0.3VA/circuit(when it is rated input)
AC current: <0.2VA/phase(when it is rated input)
 Output interface capability
Continuous power: 6A (DC)
Switched current: 20A (DC)
Breaking capacity (10,000times of operation, L/R=40ms):5A/48VDC or 1A/220VDC
---(trip). (Overload relay)
1A/48VDC, 0.15A/220VDC
---(signal). (Signal relay)
Actuation time: <5 ms
Switching value input
Insulation voltage rating: 5kVDC
Rated voltage value: 110/220VDC or VAC, allowable deviation ±20℅;
24/48 VDC, allowable deviation ±20℅.
Current consumption: <3m A /circuit.
Filtering time: 0ms~999ms can be set, Filtering time will not affect the ACcurACy of recording time
Communication
Insulation voltage rating: 2kV DC (except RS232)
RS485 port: baud rate 1200、2400、4800、9600、19200、38400 are optional
Communication protocol: IEC60870-5-103protocol、Modbus、DNP3.0, see appendix of communication part
RS232: baud rate is fixed at 19200, exclusive for PLPShell. Non-public communication protocol
Communication media: GSM or GPRS wireless communication can be used, specific
operation requires consultation with the manufacturer.
RJ45:TCP/IP Modbus TCP 、DNP3.0,
AC sampling and processing
filtering circuit: second-order low-pass filtering,cut-off frequency is 700 Hz, quality factor is 0.707.
Software filtering: full-cycle cos frequency
Sampling frequency: 32 point/cycle
Actuation interval of protection and control algorithm: 1/4cycle
Actuation interval of measuring algorithm: 1cycle
Actuation precision of steady-state protection and control
Phase current element: ±3℅
Voltage element: ±3℅
Phase angle: ±2°
Frequency element: ±0.01 Hz
Slip: ±0.1 Hz/S
time element: ±15 mS (1.2times setting value, includes export time)
Fixed Actuation time <35 mS
13
Curve timing of inverse time limitation: ±5℅ or ±40 mS
Coefficient of over-value return: 0.98
Coefficient of under-value return: 1.02
Precision of measurement and metrology
Phase current: ±0.2℅
Voltage: ±0.2℅
Phase angle: ±0.5°
Rate fACtor: ±0.5℅
Frequency: ±0.01 Hz
Power: ±0.5℅
KWh: ±0.5℅
Temperature coefficient: ±2ppm/(℃)²
Ambient conditions
Temperature range of operation: -20℃~+65℃
Temperature range of transportation and storage -35℃~+70℃
Humidity: 15℅~95℅ non-condensing
IEC60068-2-2 dry heat testing
IEC60068-2-1 dry cold testing
Cyclic damp heat test: IEC60068-2-30, relative humidity >93℅,T=20~65℃
Storage temperature testing: IEC60068-2-48
Insulation performance(IEC 60255-5)
2kV, 50 Hz/1minute Dielectric strength (between the loop and ground, between the independent circuits):
2kV, 50 Hz / 1 minute
Impulse withstands voltage: ±5kV (1.2/50us, 0.5J)
Insulation resistance: >100MΩ, 500VDC
Mechanical testing
IEC60255-21-1: 1 stage
Impact testing: IEC60255-21-2: 1stage
Earthquake testing: IEC60255-21-3:2 stage
Electromagnetic compatibility
Anti-interference towards high-frequency: IEC 60255-22-1: 3stage(1MHz,2.5kV common-mode and 1.0kV
differential-mode)
Anti-static discharge: IEC 60255-22-2: 4 stage (± 8kV contact discharge)
Anti-frequency magnetic interference IEC 1000-4-8: 5stage(100A/m)
Anti-radiated electromagnetic field interference IEC 60255-22-3: 3stage(10V/m, f=80~1000M Hz)
Anti-fast transient disturbance interference: IEC 60255-22-4: 4stage (2.5kHz & 5kHz,±4kV)
Anti-surge interference: IEC 1000-4-5: 4stage(±5kV common-mode, ±2kV differential-mode )